Features
- Output & input over voltage protection
- Second output with series diode
- Over and undervoltage alarm with relay output
EMC, Safety & Environment base for CE mark
- EN60950 class I
- EN61000-6-3 Emission
- EN61000-6-2 Immunity
- EN/IEC61000-4-4, 4kV
- EN/IEC61000-4-5 level 2 & 3
- RoHS compliant (can optionally be lead soldered)
Input voltage rating
Nominal input
|
Input voltage range
|
Code
|
|
24 Vd.c.
|
18 - 32V
|
24
|
|
48 Vd.c.
|
38 - 60V
|
48
|
|
110, 127 Vd.c.
|
88 - 150V
|
110
|
|
220, 250 Vd.c.
|
175 - 300V
|
220
|
Input voltage ranges that meets
Railway standard EN50155/IEC60571, can be provided on request.
Output voltage
|
Current
|
Power
|
|
24V
|
9 - 10A
|
216 - 240W
|
|
36V
|
6.7A
|
240W
|
|
48V
|
4.5 - 5A
|
216 - 240W
|
|
60V
|
3.6 - 4A
|
216 - 240W
|
|
110V
|
1.97 - 2.2A
|
216 - 240W
|
Output voltage ratings and product code
|
Output
|
Input voltage range
|
Voltage
|
Current
|
Power
|
10 - 30V
|
20 - 60V
|
50 - 150V
|
90 - 270V
|
|
24V
|
9.0A
|
216W
|
PM240 24/24
|
|
|
|
|
24V
|
10.0A
|
240W
|
|
PM240 48/24
|
PM240 110/24
|
PM240 220/24
|
|
36V
|
6.7A
|
240W
|
|
PM240 48/36
|
|
|
|
48V
|
4.5A
|
216W
|
PM240 24/48
|
|
|
|
|
48V
|
5.0A
|
240W
|
|
PM240 48/48
|
PM240 110/48
|
PM240 220/48
|
|
60V
|
3.6A
|
216W
|
PM240 24/60
|
|
|
|
|
60V
|
4.0A
|
240W
|
|
PM240 48/60
|
PM240 110/60
|
PM240 220/60
|
|
110V
|
1.97A
|
216W
|
PM240 24/110
|
|
|
|
|
110V
|
2.2A
|
240W
|
|
PM240 48/110
|
PM240 110/110
|
PM240 220/110
|
How to read our product code:E.g. PM240 110/24
PM240 = family code
110 =input voltage rang code110
24 =output voltage24V